Model: Cummins C3000D5
Standby Power: 2400 KW 3000 KVA
Prime power: 2200 KW 2750 KVA
Engine: QSK78-G9
Alternator: LVSI804T
3000kva C3000D5 main parameters |
|||
Unit Type | C3000D5 | ||
Performance parameters | Backup (ESP) | Normal load (PRP) | |
in accordance withISO 8528 | |||
power(kWe) | 2400 | 2200 | |
capacity(KVA) | 3000 | 2750 | |
Fuel consumption(H) | 496.5liters (normal load100%under load) | ||
engine model | QSK78-G9 | ||
Generator model | LVSI804T | ||
Controller model | PC3.3 | ||
Manufacturer | Cummins Power (China) Co., Ltd. | ||
Special function options | ·Parallel Interface Kit·coolant heater·coolant level sensor | ||
·Ball Winding Temperature Sensor·electric ball heater· PMGpermanent magnet motor | |||
3000kva C3000D5 Product Description |
|||
Cummins Power (China) Co., Ltd. is Cummins Power’s only generator set manufacturer in China. The products produced adopt Cummins Power’s global unified design, production and testing standards and are manufactured in China. Provide comprehensive quality assurance and provide one-stop service for the main components of the generator set, including the engine, generator and control system. | |||
·conform toISO8528-2005andGB/T2820-2009″Reciprocating internal combustion engine driven alternator sets” standard. | |||
·The design and manufacturing units of the generator set have passedISO9001orISO9002Certification. | |||
·Provided by Cummins1year or1000Operating hour quality assurance, responsible for the entire generator set warranty, including the engine, generator and control system. | |||
·A nationwide professional service network provides customers withtwenty fourHours of after-sales service and technical support. | |||
3000kva C3000D5 Requirements |
|||
Altitude(m) | ≤1000(More than required power correction) | water qualityPHvalue | 6.5~8 |
fuel standards | 0#Light diesel oil | Relative humidity | ≤ 60% |
Atmospheric pressure(kPa) | ≥89.9 | Surface mold growth level | GB/T2423.16/2class |
Engine oil standards | CFclass/15W-40or above | Earthquake resistance | horizontal acceleration0.2gvertical acceleration0.1g |
Intake air temperature(℃) | ≤40 | earthquake relative intensity | Chinese standard8class |
Note: All data in this data sheet are obtained when the engine is running with a fuel pump, water pump, oil pump, air filter and muffler, but does not include the alternator, air compressor, fan, optional equipment and driving parts. All data are based onSAE J1349Standard conditions-ocean90m(300ft.), atmospheric pressure100kPa(29.61in.Hg),Intake air temperature25℃(77°F), water vapor pressure1.0kPa(0.30in.Hg), use standard2#Diesel or comply withASTM D2of diesel. Data are subject to change at any time without notice. | |||
3000kva C3000D5 Generator set parameters |
|||
Unit type | Open frame type (optional: silent type, mobile type) | Rotating speed(r/min) | 1500 |
Unit Type | C3000D5 | Emission Standards | National Three |
Backup power(kWe) | 2400 | frequency(Hz) | 50 |
Normal load power(kWe) | 2200 | Voltage(V) | 400 |
Unit size(mm) | 7180x2384x3403 (LWH) | circuit breaker switch | none |
Unit weight(kg) | 24709 | Random accessories | Industrial muffler, bellows, engine oil, starting battery |
Cummins Power is the world’s leading manufacturer in the design and manufacturing of pre-integrated generator sets from 55kVA to 2750kVA. All major components of the unit – engine, alternator, transfer switch and control system – are designed and manufactured by Cummins. We call this integration The Power of OneTM, this production method means that every component of the generator set is designed to work harmoniously with the entire unit from the beginning. | |||
3000kva C3000D5 Diesel engine parameters |
|||
Diesel engine brand | CumminsCummins | Fuel System | electronic injection |
Diesel engine model | QSK78-G9 | cooling method | Closed water cooling cycle |
Diesel engine power (kWm) | 2388 | Governor type | electric |
Number of cylinders/Cylinder displacement | 16/Vtype | Start mode | DC24Velectric start |
Compression ratio | 14.5:1 | Air intake method | Turbocharging, low temperature intercooling |
Bore diameter×journey(mm) | 159×190 | Radiator temperature | 40℃ |
Displacement(L) | 60.2 | Engine oil temperature (℃) | 121 |
hydraulics pressure(kPa) | 345~483 | Configuration | cast iron,60°,Four-stroke |
Oil capacity(L) | 397 | Rotating speed(r/min) | 1500 |
Engine coolant capacity(L) | 193.1 | idling(r/min) | 725~775 |
Water tank coolant capacity(L) | 409.7 | Speed limit(r/min) | 1725±50 |
The entire series uses Cummins engines as power, with outstanding transient response characteristics, good fuel economy, environmentally friendly emissions, high reliability and long life cycle. With rugged and durable design and reliable electromechanical performance, Cummins products can also be applied to distributed power generation facilities in peaking power plants, peak shaving (or peak shaving) and power management at large commercial or industrial production sites. | |||
3000kva C3000D5 Generator parameters |
|||
Generator brand | StamfordStanford | temperature rise | 125℃ |
Generator model | LVSI804T | Power Factor | COSΦ=0.8lag |
Type | Brushless, single bearing, rotating magnetic field | Telephone harmonic coefficient:THF | 2% |
Excitation system | Permanent magnet, automatic voltage adjustment | Telephone interference coefficient:TIF | <50 |
Winding structure | 2/3Pitch | Wiring | Y Type connection method |
Phase | Three-phase four-wire | Protection level | IP23 |
Insulation level | Hclass | radio interference | satisfyBS800andVDEofG,Nclass |
cooling system | direct drive centrifugal fan | Applicable environment | less than altitude1km,40℃ambient temperature |
fulfill the standard | conform toGB755,BS5000the third part,VDE0530,NEMA MG1-22,IEC-34,CSAC22-100andAS1359 | ||
The entire series uses Stanford generators, which have excellent excitation characteristics, allowing the diesel generator set to withstand high-power instantaneous loading, with small voltage fluctuations and rapid recovery. Alternators manufactured by Cummins rely on their high performance and low impedance.Provides excellent voltage waveform and motor starting performance in applications with high power supply requirements, such as data centers, hospitals and industrial facilities. | |||
3000kva C3000D5 Control system parameters |
|||
Controller model | PC3.3 | panel | LCD,ledBacklight indication |
Type | Power Commanddigital | Operation surface facing | Device side |
language | Multiple countries (including Chinese and English) | voltage regulation | Digital three-phase voltage detection, full-wave rectification |
interface | PCCNetandModbus | Monitoring and protection | Real-time full-process monitoring, can support remote |
Power supply | 12Vand24DCbattery | extensions | Extended parallel connection (peak shaving/base load) distribution function |
Switch system (AMF) | Load switching operations can be realized in open switching, closed switching, and soft switching (ramp) modes. | ||
Standards compliant | conform toUL,NFPA,ISO,IEC,Mil Std,CEandCSAstandard | ||
Power Command®The control system is a microprocessor-based generator set monitoring, metering and control system designed to meet the needs of generator sets powered by Cummins engines. This control system provides a convenient and concise human-machine interface for the generator set, realizing digital voltage regulation, digital speed regulation and engine set protection. All control functions are integrated into a single control system, which has higher performance than traditional generator set control systems. performance and reliability. The control system has been designed and tested taking into account the harsh conditions found in typical generator set applications. | |||
3000kva C3000D5 Installation parameters |
|||
Minimum ventilation volume(m3/s) | 48.6 | Minimum computer room area(mm) | 9000×6000×3500(LWH) |
Combustion air volume(m3/s) | 2.7 | Air duct length(mm) | 600 |
Minimum air inlet area(m2) | 9.9 | height above ground(mm) | ≈700 |
minimum discharge area(m2) | 8.2 | Smoke exhaust pipe height(mm) | 3000 |
Water tank exhaust outlet size(mm) | 2344×2815 | cement foundation thickness(mm) | >150 |
Daily fuel tank capacity(L) | 1000 | Maximum back pressure(kPa) | 6.8 |
Note: The installation should be adapted to local conditions according to the site conditions. Except for the fixed parameters of the equipment, the installation data in the table are conventional data recommended by Cummins. Please inform the user. | |||
Cummins C3000D5 generator, Cummins C3000D5 diesel generator, Cummins C3000D5 generator specifications, Cummins C3000D5 generator price, Cummins C3000D5 generator manual, Cummins C3000D5 generator for sale, Cummins C3000D5 generator parts, Cummins C3000D5 generator service, Cummins C3000D5 generator maintenance, Cummins C3000D5 generator warranty, Cummins C3000D5 generator efficiency, Cummins C3000D5 generator noise level, Cummins C3000D5 generator fuel consumption, Cummins C3000D5 generator installation, Cummins C3000D5 generator rental, Cummins C3000D5 generator troubleshooting, Cummins C3000D5 generator start-up, Cummins C3000D5 generator installation cost, Cummins C3000D5 generator repair, Cummins C3000D5 generator battery, Cummins C3000D5 generator service manual, Cummins C3000D5 generator control panel, Cummins C3000D5 generator emissions, Cummins C3000D5 generator technology, Cummins C3000D5 generator efficiency improvements, Cummins C3000D5 generator reliability, Cummins C3000D5 generator maintenance checklist, Cummins C3000D5 generator lifespan, Cummins C3000D5 generator power output, Cummins C3000D5 generator fuel efficiency, Cummins C3000D5 generator features, Cummins C3000D5 generator benefits, Cummins C3000D5 generator user manual, Cummins C3000D5 generator specifications and features, Cummins C3000D5 generator reliability reviews, Cummins C3000D5 generator fuel tank capacity, Cummins C3000D5 generator oil type, Cummins C3000D5 generator maintenance cost |
Auxiliary system | Distribution system | Environmental protection engineering | Maintenance consumables | Spare parts |
● Water jacket heater | ● Dual power conversion cabinet | ● Particle trap | ● Cooling liquid | ● Speed control board |
● Oil heater | ● Parallel cabinet | ● Water bath exhaust purifier | ● Lubricating oil | ● Adjusting pressure plate |
● Anti condensation heater | ● Grid connected cabinet | ● Sound insulation and noise reduction engineering for computer rooms | ● Air filter | ● Fan belt |
● Oil water separator | ● Grounding resistance cabinet | ● Water cooling engineering | ● Oil filter | ● Controller |
● Daily fuel tank | ● DC screen | ● Water tank remote installation project | ● Diesel filter | |
● PT cabinet | ● Water filter |
Generator set model | Standby power(KW) | Normal load(KW) | Engine model | Engine power(KW) | Generator model | Controller | Fuel consumption (normal load) L/H |
C55D5 | 44 | 40 | 4BTA3.9-G2 | 55 | UCI224D1 | PC1.1 | 129 |
C80D5 | 64 | 58 | 6BT5.9-G1 | 92 | UCl224F1 | PC1.1 | 163 |
C90D5 | 72 | 65 | 6BT5.9-G1 | 92 | UCI224G1 | PC1.1 | 182 |
C100D5 | 80 | 73 | 6BT5.9-G1 | 92 | UCl274C1 | PC1.1 | 20 |
C110D5 | 88 | 80 | 6BTA5.9-G2 | 145 | UCI27401 | PC1.1 | 27 |
C150D5B | 120 | 110 | 6BTAA5.9-G15 | 160 | UCI274E1 | PC1.2 | 32 |
C175D5B | 140 | 127 | 6BTAA5.9-G15 | 160 | UCI274F1 | PC1.2 | 38 |
C200D5 | 160 | 145 | 6CTA8.3-G2 | 180 | UCI274H1 | PC1.1 | 42 |
C220D5 | 176 | 160 | 6CTAA8.3-G7 | 203 | UCl274H1 | PC1.2 | 45 |
C250D5 | 200 | 182 | 6CTAA8.3-G9 | 231 | UCDI274J1 | PC1.2 | 51 |
C275D5B | 220 | 200 | 6LTAA9.5-G3 | 280 | UCDI274K1 | PC1.2 | 54 |
C300D5B | 240 | 220 | 6LTAA9.5-G3 | 280 | S4L1D-D41 | PC1.2 | 58 |
C330D5B | 264 | 240 | 6LTAA9,5-G1 | 320 | S4L1D-D41 | PC1.2 | 66 |
C350D5B | 280 | 256 | GLTAA9.5-G1 | 320 | S4L1D-E41 | PC1.2 | 70 |
C400D5 | 320 | 288 | QSG12-63 | 369 | S4L1D-F41 | PC2.2 | 72 |
C450D5 | 360 | 328 | QSG12-G4 | 409 | S4L1D-G41 | PC2.2 | 82 |
C400D5EB | 320 | 291 | QSZ13-G7 | 419 | SSL1D-C41 | PC2.2 | 80 |
C450D5EB | 360 | 327 | QSZ13-G7 | 419 | S5L1D-C41 | PC2.2 | 89 |
C500D5 | 400 | 364 | QSZ13-G5 | 469 | S5L1D-D41 | PC2.2 | 93.2 |
C550D5 | 440 | 400 | QSZ13-G10 | 509 | S5L1S-D41 | PC2.2 | 93.1 |
C550D5E | 440 | 400 | QSX15-G8 | 500 | SSL1D-D41 | PC2.2 | 104.2 |
C640D5 | 512 | 466 | KTAA19-G6 | 570 | SSL1D-E41 | PC1.2 | 131 |
C700D5 | 565 | 512 | VTA28-G5 | 612 | SSL1D-F41 | PC1.2 | 140 |
C825D5 | 660 | 600 | VTA28-G6 | 733 | S6L1D-C41 | PC1.2 | 147 |
C900D5 | 720 | 656 | OSK23-G3 | 768 | S6L1D-D41 | PC3.3 | 163.8 |
C1000D5 | 850 | 810 | KTA38-G5 | 970 | S6L1D-E41 | PC3.3 | 207 |
KTA38-G14 | |||||||
C1100D5B | 906 | 823 | KTA38-G5 | 970 | S6L1D-F41 | PC3.3 | 209 |
KTA38-G14 | |||||||
C1250D5A | 1000 | 900 | KTA38-G9 | 1089 | S6L1D-G41 | PC3.3 | 254.4 |
C1400D5 | 1120 | 1000 | KTA50-G3 | 1227 | S6L1D-H41 | PC3.3 | 261.2 |
C1675D5A | 1340 | 1200 | KTA50-GS8 | 1429 | S7L1D-D41 | PC3.3 | 308.6 |
C1875D5E | 1500 | 1360 | QSK50-G15 | 1649 | S7L1D-F41 | PC3.3 | 346 |
C2000D5 | 1650 | 1500 | QSK60-G3 | 1790 | S7L1D-G41 | PC3.3 | 354 |
S9H1D-A41 | |||||||
C2000D5EB | 1600 | 1500 | QSK50-G16 | 1758 | S7L1D-G41 | PC3.3 | 361 |
C2250D5 | 1800 | 1600 | QSK60-G4 | 1915 | S7L1D-H41 | PC3.3 | 389 |
S9H1D-B41 | |||||||
C2250D5E | 1800 | 1600 | QSK50-G17 | 1972 | S7L1D-H41 | PC3.3 | 406 |
S9H1D-B41 | |||||||
C2500D5A | 2000 | 1800 | OSK60-G8 | 2145 | S7L1D-J41 | PC3.3 | 446 |
S9H1D-C41 | |||||||
C2750D5B | 2200 | 2000 | QSK60-G22 | 2351 | LVSI804T1 | PC3.3 | 496.5 |
S9H1D-D41 | |||||||
C3000D5 | 2400 | 2200 | QSK78-G21 | 2613 | LVSI804W2 | PC3.3 | 572 |
S9H1D-D42 |
Cummins Power Generaton,Cummins Generator Sets,Cummins Diesel Generators,Cummins Marine Generator Set,Cummins Gensets,Industrial Generators,Silent Generator,Cummins Container Generator Sets,Soundproof Generator,Cummins Trailer Generator
Cummins Power Generaton,Cummins Generator Sets,Cummins Diesel Generators,Cummins Marine Generator Set,Cummins Gensets,Industrial Generators,Silent Generator,Cummins Container Generator Sets,Soundproof Generator,Cummins Trailer Generator XML